The HRN-36 Monitoring Relay is used to monitor the voltage level in a DC supply range. The monitored voltage is also the supply voltage. It is possible to set 2 independent levels with the relay.
To avoid short-term peaks, there is a delay that can be set in the range 0.5-10s. This comes into effect when the device switches from the normal state to the fault state and avoids unnecessary switching of the output relays. When resetting to the normal state, this delay no longer comes into effect, but the hysteresis (5%) does. The changeover contacts provide further configurations and functions depending on the current requirements of the application.
Electrical Data
| Operating and monitoring voltage | DC 6-30 V |
| Power consumption | 0,35W max. 0,5W |
| Upper voltage level (Umax) | 12-30V |
| Lower voltage level (Umin) | 50-95% von Umax |
| Max. continuous voltage | DC 36V |
| Peak overload (1s) | DC 48V |
| Time delay | 0.5-10s |
| Setting accuracy | 5% - mechanical setting |
| Hysteresis | 5% |
| Output | Relay 1 changeover contact |
| Contact material | AgNi |
| Nominal current | 16 A/AC1 |
| Breaking capacity | 4000 VA/AC1, 384 W/DC1 |
| Switching output | 250V AC1 / 24V DC |
| Power loss (max.) | 1.2W |
| Mechanical life | 10.000.000 op. |
| Electrical life (AC1) | 100.000 op. |
| Connection | Screw terminals 2.5mm² |
| Ambient temperature | -20°C to +55°C |
| Storage temperature | -30°C to +70°C |
| Protection class | IP40 front / IP20 terminals |
| Voltage limitation class | III |
| Pollution degree | 2 |