Skip to main content Skip to page footer

Voltage Monitoring Relay HRN-36

Voltage Monitoring Relay with the range DC 6-30V.
Adjustable monitoring range:
Umax 12-30W, Umin 50-95% of Umax

Quick Facts

  1. Monitoring of an adjustable voltage range
  2. Supply voltage from monitored voltage DC 6-30V
  3. Max range 12-30W
  4. Min range 50-95% of Umax
  5. Delay 0.5-10s adjustable

The HRN-36 Monitoring Relay is used to monitor the voltage level in a DC supply range. The monitored voltage is also the supply voltage. It is possible to set 2 independent levels with the relay.

To avoid short-term peaks, there is a delay that can be set in the range 0.5-10s. This comes into effect when the device switches from the normal state to the fault state and avoids unnecessary switching of the output relays. When resetting to the normal state, this delay no longer comes into effect, but the hysteresis (5%) does. The changeover contacts provide further configurations and functions depending on the current requirements of the application.

Electrical Data

Operating and monitoring voltage DC 6-30 V
Power consumption 0,35W max. 0,5W
Upper voltage level (Umax) 12-30V
Lower voltage level (Umin) 50-95% von Umax
Max. continuous voltage DC 36V
Peak overload (1s) DC 48V
Time delay 0.5-10s
Setting accuracy 5% - mechanical setting
Hysteresis 5%
Output Relay 1 changeover contact
Contact material AgNi
Nominal current 16 A/AC1
Breaking capacity 4000 VA/AC1, 384 W/DC1
Switching output 250V AC1 / 24V DC
Power loss (max.) 1.2W
Mechanical life 10.000.000 op.
Electrical life (AC1) 100.000 op.
Connection Screw terminals 2.5mm²
Ambient temperature -20°C to +55°C
Storage temperature -30°C to +70°C
Protection class IP40 front / IP20 terminals
Voltage limitation class III
Pollution degree 2

Design, Dimensions, Weight

Design DIN rail plastic housing light grey, snap-on on 35mm DIN rail 1 HP
Dimensions WxHxD 17.6x90x64mm
Weight 60g

Ordering Data and Conformity

Type designation HRN-36
Article no. EL200156
Make Elko
Conformity CE

Potentiometers

PotentiometerFunction
FUNCSetting the function / operating states
Umax [V]Setting the upper level Umax
Umin [%Umax]Setting the lower level Umin
t [s]Setting the delay

Function Indicators (LEDs on the Module)

greenredMeaning
ONOFFNormal state
ONONExceeding Umax (overvoltage)
OFFONUnderrun Umin (undervoltage)

Pin Assignment

3-pole connector top

A1 Supply AC 48 - 276 V
R Control input (RESET)
A2 Supply AC 48 - 276 V

3-pole connector below

15 Switching output 250V (root)
16 Switching output 250V (NC)
18 Switching output 250V (NO)